FireLoop seismic joint for fire sprinkler systems

FireLoop

The FireLoop seismic joint moves in all directions to protect your fire sprinkler system during a seismic event or building settlement. Installs fast and easy with just to connections and a single hanger.
Learn more ►

Installation instructions for Fire Drop flexible armovers for fire sprinklers

Flexible drop sizes

Available Lengths:
28-inch
40-inch
48-inch
59-inch
71-inch

Reducers: 1/2-inch and 3/4-inch

Fire drop technical data

Download tech sheet >

Rated Pressure: 200 psi

Max Ambient Temp: 150°

Maximum Sprinkler K-factor for 1/2 inch outlet: 8

Maximum Sprinkler K-factor for 3/4 inch outlet: 14

Suitable for use in Wet & Dry Systems, UL 2443

Minimum Bending Radius:
5 inches (190mm)

Maximum Bends:
71-inch (1800mm): 3 bends
59-inch (1800mm): 3 bends
48-inch (1500mm): 3 bends
40-inch (1200mm): 1 bend
28-inch (610mm): 1 bend

The FireDrop Flexible Sprinkler Hose is an innovative product designed to save installation time. The FireDrop Flexible Sprinkler Hose is designed in accordance with NFPA 13, 13D, and 13R, tested and approved by Underwriters LabŪ under UL 2443.

The anchoring components of the FireDrop are intended for use with drop ceilings, such as intermediate and heavy duty ceilings as described in ASTM C635 (Standard Specification for the Manufacture, Performance, and Testing of Metal Suspension Systems for Acoustical Tile and Lay-in Panel Ceilings) and ASTM C636 (Standard Practice for Installation of Metal Ceiling Suspension Systems for Acoustical Tile and Lay-in Panel).

Download installation instructions (pdf)

Step 1

Connecting the reducer

  1. Disconnect the reducer (Figure 1) from the flexible hose by turning the nut.
  2. Verify plastic ring and rubber gaskets are in place (Figure 1).
  3. Reconnect the reducer to the flexible sprinkler hose by turning the nut (Figure 2).
  4. Tighten the nut to ensure the leak-proof connection, torque to 24 ft-lbs (approximately hand tight + ¼ turn) (Figure 2).

Step 2

  1. Disconnect the nipple from the flexible sprinkler hose.
  2. Connect the tapered NPT end of the nipple to the main sprinkler pipe with pipe joint compound or Teflon tape to ensure a leak-free connection and tighten it (Figure 3).
  3. Verify the plastic ring and rubber gasket are in place (Figure 4).
  4. Connect the flexible hose to the nipple by tightening the nut (Figure 4) torque to 21 ft-lbs (approximately hand tight + ¼ turn).

Step 3

Connecting the square bar to the ceiling structure

  1. Assemble the centering bracket and the two end-brackets to the square T-bar (Figure 5) place the end- brackets on the ceiling rails as shown (Figure 6).
  2. Push the end-brackets onto the ceiling rail, check that the end-brackets are properly seated (Figure 6), maximum spacing for the end bracket is 60 inches and minimum 24 inches.
  3. Tighten the bolts on the top of the end-brackets firmly. Torque to 3 ft-lbs (Figure 5).
  4. Tighten the bolts on the side of the end-brackets. Torque to 3 ft-lbs.

Step 4

  1. Place the reducer inside the centering bracket by bending the hose in as smooth and large an arc as possible (Figure 7). NOTE: Do Not Bend the Hose Within 2-1/2" of End Connection.
  2. Install sprinkler head in the reducer (install per sprinkler head manufacturer installation instructions). Put a wrench on the reducer to prevent twisting of the hose.
  3. Position and lock the centering bracket and tighten the bolts (Figure 8) torque to 5 ft-lbs.

Top